L2234
L2778
L4681
L5179
Emax
45/161
Doc. No
Model
Apparatus
Scale
Page No
1SDH000460R0002
L5439
12.5. User interface
Captions on the front of the PR121/P unit:
123
45
68
10
79
11 12
14
13
15
16
17 18
19
20
21 22
23 24
25
26
27
Ref. Description
1 Alarm indicator LED for protection function L
2 Pre-alarm indicator LED for protection function L
3 Alarm indicator LED for protection function S
4 Alarm indicator LED for protection function I
5 Alarm indicator LED for protection function G
6 DIP switch for fine-setting of current threshold l1
7 DIP switch for the main setting of the current threshold l1
8 DIP switch for setting current threshold l2
9 DIP switch for setting current threshold l3
10 DIP switch for setting current threshold l4
11 DIP switch for setting trip time t1
12 DIP switch for setting trip time t2 and type of curve
13 DIP switch for setting trip time t4 and type of curve
14 Position indicator for the DIP switches for the mains frequency
15 Position indicator for the DIP switches for setting the neutral protection
16 Rating plug
17 Position indicator for the DIP switches for setting the threshold I1
18 Position indicator for the DIP switches for setting the threshold I2
19 Position indicator for the DIP switches for setting the threshold I3
20 Position indicator for the DIP switches for setting the threshold I4
21 Position indicator for the DIP switches for setting the time t1
22 Position indicator for the DIP switches for setting the time t2
23 Position indicator for the DIP switches for setting the time t4
24 DIP switch for setting the mains frequency and adjusting the neutral protection
25 "i Test" test and info button
26 Test connector for connecting or testing the release using an external device (PR030/B battery unit, BT030 USB
wireless communication unit and SACE PR010/T unit)
27 Serial number of the PR121/P protection release
12.5.1. Trip Test
Before you start, it is advisable to run a test (“Trip Test”) on the whole TC chain by pressing and holding the button “i Test” for
at least 7 s. A positive outcome is shown by the circuit-breaker opening (see Watchdog). To be able to do the test, you need to
connect the PR030/B battery unit.
12.5.2. Initial settings
ABB SACE will see to applying the adhesive labels on the PR121/P for all the variables relating to the circuit-breaker (e.g. Type
of circuit-breaker, Rating Plug size, etc.).
It should be noted that ABB SACE provides a sensible definition for each possible setting (see par. 12.5.4).
WARNING: Before putting the PR121/P into service, it is nonetheless absolutely essential for the user to care-
fully define each parameter that can be changed.